Lenze drives run thousands of European packaging lines, conveyors and material-handling machines — the older 8400 family (BaseLine, StateLine, HighLine, TopLine) and the newer i500 series (i510/i550). When one trips, the keypad shows a short alphanumeric code (OU, LU, OC1, OH…) on the 8400, or a five-digit number (3210, 4310…) on the i500. This guide explains the codes technicians meet most often, what Lenze’s official manuals say causes them, and the step-by-step repairs that get the line running again. Browse our current Lenze and general-purpose inverter stock for same-day replacements.
On the 8400 series, every error message has a short name (e.g. OC1) plus an internal number such as [xx.0123.00016]. Each message has a configurable response — None, Warning, Trouble or Fault — set through C-parameters, and every event is written to the drive’s Logbook. On the i500, errors are numeric CiA-402 style codes shown on the keypad and stored in the error history buffer. A Warning does not stop the drive, a Trouble limits operation, and a Fault blocks pulses until the cause is fixed.
Fault manifestations. The drive trips during deceleration or when an overhauling load pushes energy back into the DC bus. The keypad shows OU; if the overvoltage stays active longer than the time set in C00601, a full “Fault” is tripped and the output is switched off.
Root causes. Regenerative energy from high-inertia loads during fast stops, deceleration ramps that are too short, a missing or undersized brake resistor, or an abnormally high mains voltage.
Repair steps. Measure the DC bus voltage while decelerating; extend the ramp-down time; connect or verify the external brake resistor and brake energy management settings; for frequent regenerative duty, use a regenerative power supply module or link several drives on a common DC bus. After the trip, note that the auto-start lock (C00142) may keep the drive from restarting until controller inhibit is toggled.
Fault manifestations. The drive trips at power-up or collapses under heavy load because the motor control can no longer be supplied.
Root causes. Mains dips or interruptions, blown input fuses, loose supply terminals, or an undersized supply cable.
Repair steps. Measure all three input phases under load; check fuses and tighten terminals; verify the DC-bus supply path; adjust C00142 if the auto-start lock behavior is unwanted.
Fault manifestations. An immediate trip, often right at controller enable, with the inverter control switched off to protect the electronics.
Root causes. Short-circuited motor phases — most often incorrectly executed motor connections — a wrong device/motor power combination, or current-limit (Imax) controller dynamics set too high. Lenze’s own application knowledge base adds two traps: on firmware below 14.00, resetting OC1 in less than 3 seconds with the motor terminals still bridged can destroy the device, and on firmware below 12.00 low-inductance synchronous motors can cause false OC1 trips right after enable.
Repair steps. Disconnect the motor and inspect connections and the device plug connector; test the motor and cable insulation; only use permissible device/motor power combinations; reduce the dynamics of the current-limit controller; reset the error at least 3 seconds after the trip, after checking wiring.
Fault manifestations. The drive detects leakage from a motor phase to ground and blocks the output.
Root causes. Damaged cable or winding insulation; incorrect motor filter, excessive motor cable length or wrong cable shielding, which raises capacitive leakage currents to PE.
Repair steps. Megger the motor and cable to earth; replace damaged cable or motor; use the motor filters, cable lengths and shielding types Lenze recommends; verify the PE path.
Fault manifestations. A trip after running hot; the official limit temperature is fixed at 90°C. Related messages: OH3 (motor temperature contact at X106 terminals T1/T2 tripped) and OH4 (warning — heatsink is within 5°C of the shutdown point).
Root causes. Dirty filter mats or fan, blocked ventilation slots, high cabinet ambient temperature, switching frequency set too high for the environment, or insufficient mounting clearances.
Repair steps. Clean or replace the fan and filter; clean the drive; check the control cabinet temperature and cooling; reduce switching frequency; derate above 40°C ambient. For OH3, check the thermal contact wiring in the motor for open circuits.
Fault manifestations. OC5 is the device Ixt overload check tripping; OC6 is the motor thermal I2xt overload; OC12 is the brake resistor I2xt overload after frequent, long braking cycles.
Root causes. Wrong dimensioning between device, motor, resistor and the real load; load cycles that exceed the design duty; in OC6, a too-low Vmin boost (C016) in VFCplus operation can also contribute.
Repair steps. Verify dimensioning against the technical data; reduce load cycles and observe the documented duty patterns; correct Vmin boost; check brake resistor value and rating for OC12.
Fault manifestations. A warning raised during motor parameter identification.
Root causes. An interrupted motor cable, the power section switched off during identification, or implausible start parameters.
Repair steps. Check the motor cable and terminal box; rerun identification with correct nameplate data; keep the supply stable during the routine.
Fault manifestations. CE4 reports CAN “Bus off” after too many faulty telegrams; CA06 reports CAN CRC errors.
Root causes. Damaged cable or loose contact, two nodes with the same ID, wrong baud rate, missing termination, or EMC interference.
Repair steps. Check wiring and the 120Ω bus terminating resistors; give every node a unique ID; set the same baud rate on all nodes; route the bus away from power cables. The response is configurable in C592/2.
Trips only when the analog input is configured as a 4–20 mA current loop (C034/1 = 2). Check the wiring at input X4/A1U, the external 250Ω load resistor between A1U and GND, and the minimum current of the signal source.
Device-level internal errors. Switch the mains off and restart; if the message returns, the control board needs service — contact Lenze or a qualified repair station.
The i510/i550 use five-digit codes. The ones you will see most:
Clean filters and fans quarterly — most OH trips are dust, not hardware. Once a year, measure DC-bus ripple, inspect capacitor banks for bulging, and megger the motor cables. Keep CAN termination resistors tight and back up parameter sets after every change. Stocking critical spares avoids the long lead times that plague Lenze parts: we ship the Lenze E82ZBB keypad and communication module, the 8200 vector inverter E82EV552K4C200 for the installed base, and the compact SMD series inverter ESMD751X2SFA — all tested, priced and ready to move.
Can I clear OC1 by just resetting the error? No. Lenze explicitly warns that an immediate reset (under 3 seconds) of a short-circuit trip can destroy the device. Always inspect motor wiring and connectors first, then reset after at least 3 seconds.
What is the difference between Fault, Trouble and Warning responses? A Warning only records the event; a Trouble restricts operation but allows a controlled stop; a Fault blocks the output until the cause is removed and the error is reset.
My i500 shows 3210 during every deceleration. Is that the same as OU on the 8400? Functionally yes — DC bus overvoltage. Extend ramp-down times, check brake energy management, and connect a brake resistor with the chopper activated (P706.01).