By Jennifer Zhang
Panasonic's MINAS A6 family is one of the most widely installed servo platforms in modern packaging, semiconductor, and assembly machinery. The line spans single-axis pulse/analog A6B drivers such as the MADLT01SM, RTEX network A6N drivers such as the MADLT05SM, EtherCAT variants (A6ME/A6SF), and the multi-axis A6 Multi modules of the MBDLT series. All of them report faults the same way: when a protective function trips, the front-panel LED shows a code in the Er13.0 format — the number before the point is the main code, the digit after it is the sub-code — the ALM output opens, and the driver stops the motor according to Pr5.10 "Sequence at alarm."
Most alarms clear with the alarm clear input (A-CLR) held ON for 120 ms or longer after the cause is removed. Two field quirks matter: Err16.0 (overload) can only be cleared about 10 seconds after it occurs, and absolute-system alarms such as Err40.0 will not clear at all until an Absolute Clear has been performed. Panasonic's free Panaterm software shows the last 14 error factors together with the command and feedback waveforms captured at the trip moment — the fastest way to tell a wiring problem from a genuine hardware failure.
Please check our servo drive collection for tested replacement drivers and motion-control components before you begin.
Fault Manifestations: The driver refuses to run or trips during acceleration, showing Err13.0 (DC-bus under-voltage between P and N) or Err13.1 (AC interception detected — a momentary loss of input power).
Root Causes: Low incoming line voltage, one blown fuse or loose phase on a three-phase supply, undersized supply wiring, a failed upstream contactor or filter, or a supply that sags under motor inrush.
Repair Steps:
Fault Manifestations: Instantaneous trip at power-on or the first motion command. Err14.0 is over-current; Err14.1 is an IPM (intelligent power module) error detected inside the driver.
Root Causes: A short or ground fault in the motor cable (crushed conduit, coolant-wet connectors), a phase-to-phase short in the motor windings, swapped motor phases, or a failed IGBT/IPM output stage in the driver itself.
Repair Steps:
Fault Manifestations: Trip partway through a cycle after seconds or minutes of running. Err16.0 is electronic overload protection; Err16.1 is torque saturation — the driver has hit its torque limit and cannot follow the command.
Root Causes: Mechanical binding, a brake that never released, gain oscillation, a motor/driver size mismatch, or a genuine duty overload in which effective torque exceeded the overload characteristic. Remember that Err16.0 cannot be cleared until roughly 10 seconds after the trip.
Repair Steps:
Fault Manifestations: Trip during rapid deceleration or when a vertical axis lowers its load.
Root Causes: Regenerative energy flowing back into the DC bus exceeds the driver's built-in regeneration absorption — short decel times, high inertia, or high-duty vertical motion.
Repair Steps:
Fault Manifestations: Trip at power-up or intermittent trips with axis vibration. Err21.0 is encoder communication disconnection, Err21.1 a communication error, Err23.0 a communication data (frame) error.
Root Causes: Damaged encoder cable, contaminated or bent-pin connectors, noise from power cables routed in parallel, or a failing encoder inside the motor.
Repair Steps:
Fault Manifestations: The axis faults during motion because commanded position and feedback position diverge beyond the set limit (Err24.0), or the internal deviation counter overflows (Err29.0).
Root Causes: The motor stalled or slipped — mechanical jam, brake still engaged — gains set far too low, acceleration beyond available torque, or a command pulse frequency above the driver limit (pulse errors carry their own code, Err27.0).
Repair Steps:
Fault Manifestations: Trip at power-up with an EEPROM parameter error (Err36.x) or EEPROM check-code error (Err37.x).
Root Causes: Corrupted parameter memory — typically after years of vibration, repeated brownouts, or a parameter save interrupted by a power cut.
Repair Steps:
Fault Manifestations: On machines using the absolute system, the driver faults at power-up with Err40.0: encoder backup power and internal capacitor both discharged, so multi-turn data is lost.
Root Causes: Dead or disconnected absolute battery, a broken battery cable, or a machine left unpowered longer than the backup specification.
Repair Steps:
Q: The panel shows Er27.0 on a pulse-train machine. Is the driver faulty?
A: Usually not — Err27.0 is a command pulse input frequency error. Compare the controller's output pulse frequency with the driver's maximum input frequency and your electronic gear setting.
Q: Can I swap an A6B driver for an A6N (RTEX) unit?
A: Not directly. A6B accepts pulse/analog commands while A6N communicates over the RTEX network; the motion controller must match the interface type; cabling and parameters differ.
Q: Which alarms usually mean real hardware damage?
A: Err14.x, Err36–37.x, Err70.x (U/W-phase current detector errors) and encoder alarms that persist with clean wiring indicate failed hardware. Err13.0, Err16.0, Err18.0 and Err24.0 usually reflect operating conditions.
Q: Where can I get tested replacement drivers and encoders?
A: Browse our encoder collection or send us the exact model code (MADLT01SM, MADLT05SM, or your MBDLT module number) and we will quote a tested replacement with a 12-month warranty.