Why the WJ200 Trips

The Hitachi WJ200 is Hitachi's micro inverter family, covering roughly 0.1 to 15 kW in 200 V and 400 V classes with single-phase input on the small frames, a built-in EzSQ programming engine, RS-485 Modbus RTU and Safe Stop (STO) on board. When a protective function operates, the drive cuts its output and the digital operator shows an E.xx code together with a status digit — whether the drive was stopped, accelerating, decelerating or at constant speed when it tripped. Read that digit before you reset, because it decides where you look. Browse our inverter collection if you need a replacement while a drive is down.

Read the Trip Before You Reset

A WJ200 trip display is two numbers stacked: the code and the operating status at the moment of the trip. An overcurrent trip during acceleration points at ramp and load problems; the same code at constant speed points at a short, a stalled motor or a degrading output stage. Press STOP/RESET to clear a trip, or cycle the power for the codes that demand it.

E01, E02, E03, E04 — Overcurrent

Hitachi's numbering is easy to mix up: E01 is a constant-speed overcurrent, E02 deceleration, E03 acceleration and E04 an overcurrent under other conditions. Several third-party tables reorder these; the official WJ200 manual puts them in this order.

Fault manifestations. Output current exceeds the trip level and the drive shuts off instantly.

Root causes. Acceleration or deceleration time (F002 / F003) too short for the inertia; a locked or mechanically jammed motor shaft; a phase-to-phase or earth short in the motor cable; a restart into a rotating load; a degraded power module.

Repair steps. 1) Note the status digit — acceleration (E03) means start with F002 and the load; constant speed (E01) means check for a sudden mechanical seizure. 2) Lock out and megger the motor and cable with the drive disconnected. 3) Run the drive unloaded: if it still trips, the fault is inside the drive. 4) If clean, lengthen F002 / F003 in steps and confirm b012 matches the motor nameplate.

Hitachi IGBT power module, the switching device fitted inside Hitachi drives

E05 and E38 — Overload

Fault manifestations. E05 is the electronic thermal overload trip: the simulated motor heat model decides the motor is overloaded and cuts the output. E38 is low-speed overload protection for self-cooled motors that lose their fan effect below roughly 20 Hz.

Root causes. b012 left at the factory value instead of the motor's full-load current — the single most common WJ200 "fault" in the field, because the default matches the drive rating, not the motor; genuine load growth from worn bearings or product build-up; long duty at low frequency on a shaft-mounted fan motor.

Repair steps. 1) Clamp the output current and compare with nameplate FLA. 2) Set b012 to the motor FLA. 3) For continuous low-speed duty, fit a forced-ventilation motor or upsize the drive. 4) If E38 appears on a machine that has run fine for years, measure the actual current first — mechanical drag is usually the real cause.

E06 — Braking Resistor Overload

Fault manifestations. The braking circuit's duty exceeds the limit set in b090 and the drive cuts output, typically on fast stops of high-inertia loads.

Root causes. No external brake resistor fitted where the duty needs one; b090 set higher than the resistor can take; F003 too aggressive for the inertia.

Repair steps. 1) Lengthen F003 and confirm the trips stop at a slower ramp. 2) Check that a resistor is actually connected and its resistance is within the manual's allowed range for the frame. 3) Set b090 to the resistor's real duty rating. A burnt smell from the resistor box is a finding, not an atmosphere.

E07 and E15 — Overvoltage

Fault manifestations. E07 is DC-bus overvoltage from regenerative energy — it lands during deceleration, on overhauling loads, or when the supply is high. E15 is input overvoltage, checked after about 100 seconds in stop mode.

Root causes. Deceleration too fast for the inertia; no brake resistor; supply voltage running high, or capacitor switching transients on the feeder.

Repair steps. 1) Lengthen F003 and retest. 2) Fit a correctly sized brake resistor and set b090 honestly. 3) Log the supply over a shift; if it sits above rating, an input reactor or tap change is the real fix.

E09 — Undervoltage

Fault manifestations. DC bus voltage falls below the threshold and the drive trips, sometimes on every start.

Root causes. A sagging or single-phasing supply; undersized input wiring; loose input terminals; a failing bus capacitor bank on an old drive.

Repair steps. 1) Measure the supply at the drive terminals under load, not at the panel door. 2) Work back through breakers, contactor poles and terminals — one burnt contactor pole halves the supply on a single-phase-input frame instantly. 3) If the bus reads low with a healthy supply on an aged unit, the capacitors are due; weigh that against the price of a new micro drive.

Hitachi IGBT power semiconductor module

E10, E11, E22, E25, E30 — Internal Faults

Fault manifestations. E10 is a current detection system error, E11 a CPU fault, E22 a CPU communication failure, E25 a main-circuit error and E30 a driver error. These trip with no external provocation.

Root causes. Failing current sensors, corroded board connectors, severe switching noise from a poor earth, or genuine power-stage degradation.

Repair steps. 1) Power down, wait for the bus to discharge, and reseat the control connectors. 2) Verify the earth bond and cable separation — E10 and E11 that appear only when a big load starts are noise symptoms. 3) If the code is instant and repeatable with the motor disconnected, the output stage is the suspect: on Hitachi drives that means the IGBT modules and their gate drivers.

E12, E13, E14 — Terminal and Start-up Trips

Fault manifestations. E12 is an external trip from an intelligent input terminal configured as EXT. E13 is Unattended Start Protection: power was applied while a run signal was present with USP enabled. E14 is a ground fault detected during the power-up self test.

Root causes. A safety chain or PLC output wired to EXT that opened; machines restarted after a power cut with the run contact still closed; output-to-earth leakage from damaged cable, moisture or collapsed winding insulation.

Repair steps. 1) For E12, trace the EXT wiring and whatever relay drives it before blaming the drive. 2) For E13, remove the run signal before re-applying power — or disable USP deliberately if the process needs auto-restart. 3) For E14, megger the motor and cable; the protection guards the inverter, not people, so treat every E14 as a real earth fault until proven otherwise.

E21, E19, E35 — Thermal Trips

Fault manifestations. E21 is an inverter thermal trip from internal temperature above the threshold; E19 means the thermal sensor system is faulty (sensor not connected); E35 is a PTC thermistor trip from the motor side.

Repair steps. 1) Clean the heatsink fins and check the mounting space and ambient. 2) Check the derating rules at high ambient or high carrier frequency. 3) E19 on a unit that has never been opened usually means a damaged sensor connector; E35 means measure the thermistor chain at the motor terminals.

E40, E41 and the Option Codes — Communications

Fault manifestations. E40 is an operator connection fault (the remote operator was disconnected during operation); E41 is a Modbus RTU communication error. E60–E69 cover option errors, E80 an encoder disconnection, E81 excessive speed and E83 a positioning range trip.

Repair steps. 1) Reconnect the operator before power-on and inspect the connector. 2) For E41, check the RS-485 wiring, termination resistors, node addresses and the timeout settings; disable communications monitoring if the drive runs standalone. 3) For option-board codes, reseat the board and verify the master configuration; for E80, check the encoder cable first.

Maintenance That Prevents Most Trips

- Monthly: read and log every trip with its status digit and load condition. - Every 3 months: blow the heatsink fins clean, check terminal torque on R/S/T and U/V/W, and confirm the earth bond. - Every 6 to 12 months: verify b012 against the motor nameplate, listen for bearing noise, and check the supply voltage under load. - After any motor or cable change: megger the circuit and clear the trip history before restarting.

Repair or Replace

The WJ200 is inexpensive enough that economics matter: repeated E10 / E11 / E30 codes with the motor disconnected mean the output stage or a sensor is failing, and a replacement drive usually beats board-level labour on frames up to a few kW. For repair shops the power modules are the usual consumable — see the Hitachi MBN1200E25C and MBM200HT12H we stock for Hitachi drive output stages.

Hitachi power semiconductor modules, replacement parts for Hitachi drive output stages

FAQ

### What does E01 mean on a Hitachi WJ200?

An overcurrent trip at constant speed on Hitachi's numbering — not acceleration. Check the status digit, the mechanical load, and megger the motor cable before resetting.

### How do I stop repeated E05 overload trips?

Set the electronic thermal b012 to the motor's nameplate full-load current. The factory default matches the drive rating, not the motor.

### Why does E07 come back after every reset?

Reset clears the trip but not the physics: the deceleration energy still has nowhere to go. Lengthen F003 or fit a brake resistor sized for the duty.

Mitsubishi FR-E800 Inverter Fault Codes, Step-by-Step Repair & Maintenance Guide
Previous
Mitsubishi FR-E800 Inverter Fault Codes, Step-by-Step Repair & Maintenance Guide
Read More
PROFINET Communication Failure: Step-by-Step Diagnosis & Fix Guide
Next
PROFINET Communication Failure: Step-by-Step Diagnosis & Fix Guide
Read More